换流变套管末屏电压互感器波形畸变分析与处理

Analysis and Treatment for Bushing Tap TV Waveform Distortion ofConverter Transformer

  • 摘要: 为解决高压直流换流站换流变压器套管末屏互感器电压波形畸变问题, 根据故障录波波形, 从末屏电压测量环节基本回路出发, 分析出产生电压波形畸变的原因系分压式电容性电压互感器与次级电感式电压互感器配合使用时产生铁磁谐振所致。根据测量环节电路元件参数, 计算出谐振等效电感和互感器二次激磁阻抗, 并用测量法实际测量末屏电压互感器的电压与电流参数, 换算成互感器二次激磁阻抗, 证实了电压波形畸变原因分析的正确性, 验证了互感器二次激磁阻抗计算值的准确性。通过推导与分析提出消除谐振的处理措施与电路连接方法, 消除了因末屏互感器电压波形畸变导致的换流变中性点偏移, 从而消除了造成保护误动作的一大因素。

     

    Abstract: In order to solve the problem that the bushing tap TV waveform distortion of converter transformer in the high voltage DC converter stations, according to the fault recorder waveform and bushing tap voltage measurement link basic circuits, it can be obtained that the cause of voltage waveform distortion is the ferroresonance when differential pressure type capacitive voltage transformer and secondary inductive voltage transformer are applied at same time. Then resonant equivalent inductance and transformer secondary excitation impedance are calculated, and the voltage and current parameters of the bushing tap TV are actually measured according to the circuit element parameters of the measurement link circuits, which are conversed to secondary excitation impedance of transformer. So the validity of the analysis on cause of voltage waveform distortion and the accuracy of calculated value of the transformer second excitation impedance are verified. Through deducing and analyzing the measures of eliminating resonance and the circuit connection method, neutral point offset of the converter transformer caused by voltage waveform distortion of tap TV transformer is eliminated, and the protection malfunction is avoided.

     

/

返回文章
返回