Yang Daye, Yang Debo. Determination of Installed Capacity of STATCOM Considering Negative Sequence Compensation[J]. Modern Electric Power, 2010, 27(4): 22-25.
Citation: Yang Daye, Yang Debo. Determination of Installed Capacity of STATCOM Considering Negative Sequence Compensation[J]. Modern Electric Power, 2010, 27(4): 22-25.

Determination of Installed Capacity of STATCOM Considering Negative Sequence Compensation

More Information
  • Received Date: April 04, 2010
  • Revised Date: March 24, 2014
  • Published Date: August 08, 2010
  • Taking a STATCOM (Static Compensator) project of a substation in Tangshan as example, the economic STATCOM capacity under negative sequence compensation is studied in this paper. The principle of negative sequence compensation by using of STATCOM is briefly introduced firstly, and the idea of negative sequence undercompensation is presented. In addition, proportional relationship between cost and capacity is considered, and quantitative analysis of the economy under negative sequence undercompensation is carried out, from which the linear relationship between cost and required unbalanced degree ε is obtained. In the end, the simulation is carried out by PSCAD/EMTDC tool based on background project. Results Show that the proposed method for determining installed capacity of STATCOM is rational and effective.
  • 孙文骥.70t电弧炉SVC装置容量及参数的选择[J].冶金动力, 1997(3):711.[2] 王海潜.超高功率电弧炉冲击负荷引起电网电压波动值和SVC补偿容量计算方法的分析[J]. 江苏电机工程, 1999, 18(1):1823.[3] 李莉, 刘俊勇.基于容量可用率的SVC的成本回收[J].四川电力技术, 2001(4):710. [4] 钱峰, 郑健超, 汤广福, 等.利用经济压差确定动态无功补偿容量的方法[J].中国电机工程学报, 2009, 29(1):16.[5] 徐新乐.电网动态无功、三相不平衡和谐波综合治理的优化方案的研究[D].北京:华北电力大学, 2009.
  • Related Articles

    [1]WANG Junlei, WANG Shunliang, MA Junpeng, WANG Peng, HE Hailin, LIU Tianqi. Custom Modeling and Initialization of Synchronous Generating Set Based on PSCAD[J]. Modern Electric Power. DOI: 10.19725/j.cnki.1007-2322.2023.0194
    [2]WANG Min, LI Xiang, ZHANG Chengfei. The Operation and Control of Microgrid Based on the Complex Control Strategy of Multiple Inverters[J]. Modern Electric Power, 2016, 33(5): 24-29.
    [3]LIU Siwei, LI Gengyin, ZHOU Ming. Research on Transient Equivalent Modelling of Doubly fed Induction Generator Based on PSCAD[J]. Modern Electric Power, 2016, 33(2): 64-69.
    [4]CHEN Pengwei, XIAO Xiangning, YANG Yang, LI Lu. Coordinated Reactive Power Compensation Strategy for DFIG Wind Farm with STATCOM[J]. Modern Electric Power, 2016, 33(1): 8-13.
    [5]MA Weina, BAI Kai, SONG Peng, LIU Jingbo, YAO Wanye, LIU Hanmin, ZHU Si. The Research on Control Strategy of High Voltage Ride Through for PMSG Based on Dual-modes Control[J]. Modern Electric Power, 2015, 32(3): 13-18.
    [6]WANG Youchun, WEN Shanshan, QIN Yuejin, TAO Fen, CHEN Cong, HU Pan. Key Issues and Operation Simulation of the Microgrid Planning[J]. Modern Electric Power, 2015, 32(1): 8-12.
    [7]ZHANG Xue, WANG Honghua. Research on Control Strategy of Grid side Converter for Doubly Fed Wind Power Generation System Based on Single Neuron PI Controller[J]. Modern Electric Power, 2013, 30(6): 51-55.
    [8]ZHOU Shuangya, XIAO Xiangning, HAO Junwei, GAO Benfeng. Application of Frequency Scanning Method in AnalyzingSub\|Synchronous Oscillation[J]. Modern Electric Power, 2011, 28(5): 1-5.
    [9]XU Xiaoyan, SUN Jingyu. Research on Equivalence of Induction Motors During PlantPower Supply Switching[J]. Modern Electric Power, 2011, 28(3): 51-56.
    [10]XU Hao, HE Renmu, ZHOU Jingshu, ZHANG Min. Conversion of Dynamic Models from BPA to EMTDC[J]. Modern Electric Power, 2011, 28(3): 7-13.

Catalog

    Article views (905) PDF downloads (457) Cited by()

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return