闫军, 胡云鹏, 刘鉴钧, 都成刚, 姜伟基, 李博通. 结合参数辨识和牛顿插值的并网逆变器延时补偿策略[J]. 现代电力. DOI: 10.19725/j.cnki.1007-2322.2023.0135
引用本文: 闫军, 胡云鹏, 刘鉴钧, 都成刚, 姜伟基, 李博通. 结合参数辨识和牛顿插值的并网逆变器延时补偿策略[J]. 现代电力. DOI: 10.19725/j.cnki.1007-2322.2023.0135
YAN Jun, HU Yunpeng, LIU Jianjun, DU Chenggang, JIANG Weiji, LI Botong. Delay Compensation Strategy Incorporating Parameter Identification and Newton Interpolation for Grid-connected Inverter[J]. Modern Electric Power. DOI: 10.19725/j.cnki.1007-2322.2023.0135
Citation: YAN Jun, HU Yunpeng, LIU Jianjun, DU Chenggang, JIANG Weiji, LI Botong. Delay Compensation Strategy Incorporating Parameter Identification and Newton Interpolation for Grid-connected Inverter[J]. Modern Electric Power. DOI: 10.19725/j.cnki.1007-2322.2023.0135

结合参数辨识和牛顿插值的并网逆变器延时补偿策略

Delay Compensation Strategy Incorporating Parameter Identification and Newton Interpolation for Grid-connected Inverter

  • 摘要: 随着电力系统“双高”的发展趋势,可再生能源经由并网逆变器接入电网的比例不断增加,而并网逆变器引入的控制延时会改变并网逆变器阻抗特性,使并网系统存在谐振风险,危及电网安全。工程现场并网逆变器内部控制延时参数因保密而未知。针对以上问题,提出了一种结合参数辨识和牛顿插值的并网逆变器延时补偿策略。首先利用Loewner矩阵改进矢量匹配,拟合并网逆变器阻抗传递函数,由此实现并网逆变器控制延时参数的正确辨识。并基于此,给出了基于牛顿插值的补偿延时方法。通过针对性的补偿控制系统中所需要延时时间,对逆变器阻抗重塑,从而抑制系统谐振。最后通过仿真证明了文中所提方法的正确性与有效性。

     

    Abstract: With the development of "double high" in the power system, the proportion of renewable energy connected to the grid through the grid-connected inverter is increasing. However, the control delay introduced by the grid-connected inverter will change the impedance characteristics of the grid-connected inverter, causing resonance risk in the grid-connected system and threatening the security of the grid. The internal control delay parameters of the grid-connected inverter at the project site are undisclosed due to confidentiality. To address this issue, a delay compensation strategy is proposed for grid-connected inverter, which combines parameter identification and Newton interpolation. Firstly, the Loewner matrix is utilized to improve the vector matching, and an impedance transfer function of the grid-connected inverter is proposed to realize the correct identification of the control delay parameters of the grid-connected inverter. A compensation delay method based on Newton interpolation is given on this basis, which aims to reshape the impedance of the inverter by compensating the delay time required in the control system, so as to suppress the system resonance. Finally, the correctness and effectiveness of the proposed method are verified through simulation.

     

/